Remote I/O module Standard (5-pin) GC-R45

GC-R45 - Remote I/O module Standard (5-pin)

*Please note that accessories depicted in the image are for illustrative purposes only and may not be included with the product.

Software

  • CE Marking
  • UL Listing(c/us)
  • CSA

Specifications

Model

GC-R45

Maximum number of connected units

4 (GC-R45 and GC-R48 can be connected together) *1

Safety input specifications

Input device

Contact output device or PNP output device

Input type

Type3

ON level (voltage/current)

Min. 11 V/2 mA

OFF level (voltage/current)

Max. 5 V/1.5 mA

Short-circuit current

Approx. 3 mA

Protection circuit

Surge protection circuit, wrong wiring protection circuit

Maximum cable length

Max. 100 m

Safety output specifications

Output type

Maximum load current

Residual voltage (during ON)

Leakage current (during OFF)

Maximum capacitive load

Protection circuit

Maximum cable length

Test output specifications

Output type

PNP transistor output (DC-13, Type 0.5, Protected outputs) *2

Maximum load current

100 mA *2

Protection circuit

Overcurrent protection circuit *2

Maximum cable length

Max. 100 m *2 *3

AUX output specifications

Output type

PNP transistor output (DC-13, Type 0.1, protected outputs) *4

Maximum load current

100 mA

Residual voltage (during ON)

Max. 2.0 V

Leakage current (during OFF)

Max. 0.5 mA

Protection circuit

Overcurrent protection circuit

Maximum cable length

Max. 30 m

Power supply output

Supported pin

Pin 1 *2

Power supply capability

Max. 0.5 A *2

Protection circuit

Overcurrent protection circuit *2

Applicable standards

EMC

EMS: IEC 61131-2/-6, EN61131-2/-6, EMI: IEC 61131-2, FCC Part15B Class A, ICES-003, Class A

Safety

IEC 61508, EN61508 SIL3, ISO/EN13849-1:2015 Cat. 4, PL e

Dimensions

64.8×141.5×34.5 mm (W×D×H)

Power supply

Power voltage

24 VDC (-20 to +20 %) Class 2

Current consumption

Max. 90 mA

Enclosure ratings

IP65/67 (IEC 60529) (TÜV SÜD certified)

Environmental resistance

Ambient temperature

−10 to +55 °C (No freezing)

Storage temperature

−25 to +70 °C (No freezing)

Relative humidity

5 to 85 % (No condensation)

Operating altitude

Max. 2000 m

Overvoltage category

II

Pollution degree

2

Vibration resistance

Frequency: 5 to 9 Hz, Half amplitude: 3.5 mm
Frequency: 9 to 150 Hz, Acceleration: 10 m/s2
10 times each in X, Y, Z directions

Shock resistance

Acceleration: 150 m/s2, Operating time: 11 ms, 3 times each in X, Y, Z directions

Material

PBT (GF 30 %), SUS304

Weight

Approx. 420 g

*1 When connecting multiple remote I/O modules, power needs to be supplied to each remote I/O module.
*2 Power supply outputs and test outputs do not comply with paragraph 6.4.6 of IEC 61131-2.
*3 When the test output is branched and connected to multiple safety input devices, the total branched cable length must not exceed 400 m.
*4 Paragraph 6.4.6 Temporary overload of IEC 61131-2 supports up to 1.2 times the maximum load current.

Data Sheet (PDF) Other Models